Choose air- or liquid-cooling components around your thermal and mechanical requirements.

Stepped aluminum heat sink with copper contact insert — illustrative concept
Explore Thermal Technologies

Heat Sinks

Liquid Cooling

AI & Data Center Cooling

Manufacturing support for your cold plates, manifolds and cooling assemblies.

Processor cold plates and distribution manifold — illustrative concept
Explore AI Cooling

AI Compute Cooling

Distribution & Assembly

AI Cooling Interfaces
  1. Cold PlateHeat-source interface
  2. ManifoldCoolant distribution
  3. CDU InterfaceConnection requirements
  4. Rack / LoopAssembly integration
Review component fit across your cooling system.

Industry Cooling Solutions

Find components for your power electronics, energy, laser and telecom application.

Machined power module cooling plate — illustrative concept
Explore Industry Cooling

Power Electronics

EV & Energy

Laser & Telecom

Industries

High-Tech & Electronics

Components for your electronic systems.

View Industry Applications

Applications & Project Inquiries

Precision & Advanced Systems

Start with your functional and quality requirements.

View Industry Applications

Applications & Project Inquiries

Industrial & Energy

Build around your operating environment.

View Industry Applications

Applications & Project Inquiries

Materials

From prototype to production, review material performance, manufacturability and cost for your part.

Engineering Plastics

Match your polymer to function, process and environment.

→
ABS — illustrative material conceptABSReview enclosure and molding needs›Polycarbonate (PC) — illustrative material conceptPolycarbonate (PC)Discuss clarity and impact needs›Nylon (PA) — illustrative material conceptNylon (PA)Review moisture and wear conditions›POM / Acetal — illustrative material conceptPOM / AcetalReview fit and sliding features›PEEK — illustrative material conceptPEEKDiscuss operating conditions›PTFE — illustrative material conceptPTFEReview friction and chemical exposure›ULTEM / PEI — illustrative material conceptULTEM / PEIDiscuss thermal and electrical needs›

Elastomers & Specialty Materials

Confirm grade availability and application requirements.

→
Elastomers
Silicone / LSR — illustrative material conceptSilicone / LSRDiscuss flexible component needs›TPU / TPE — illustrative material conceptTPU / TPEReview flexibility and processing›EPDM — illustrative material conceptEPDMReview weathering and chemical exposure.›NBR — illustrative material conceptNBRReview oil and fuel exposure.›FKM — illustrative material conceptFKMReview temperature and chemical exposure.›
Specialty Materials
G10 / FR4 — illustrative material conceptG10 / FR4Review insulation and laminate needs›Composites — illustrative material conceptCompositesReview stiffness, weight and laminate.›Customer-Specified MaterialsConfirm your grade and requirements.›Other Specialty MaterialsDiscuss your application and grade.›
Resources

Design & Engineering

Practical guidance for your part geometry and material decisions.

Explore Design Resources

Cost & Planning

Prepare your process, budget and sourcing questions.

Explore Planning Topics

Learn & Proof

Build your knowledge before production.

Explore Learning Paths
About Us

About LK MFG

Learn who we are and how we operate.

Explore Company Information →

Get in Touch

Find our U.S. support team or start a conversation.

View All Company Information →
sales@lkmfg.com (945) 409-1013

1750 Briercroft Ct, Suite 204
Carrollton, TX 75006, USA

YOUR INTERFACES · YOUR CONDITIONS · YOUR ACCEPTANCE

Rack Cooling Interfaces
for Your Mating Ports, Alignment & Service Access

Review your machined rack adapters, mounting brackets and connection interfaces against the selected mating hardware. Define port geometry, sealing faces, alignment, service access and the supplied assembly boundary before manufacturing release.

Illustrative rack cooling interfaces assembly concept, not a customer part

Illustrative component concept

Drawing

Critical geometry & interfaces

Materials

Grades, condition & compatibility

Interfaces

Defined route & final state

Evidence

Agreed methods & records

Start with Your Mating Specification and Supplied Boundary

Define selected mating hardware, drawn parts, installation datums and acceptance ownership.

  • Identify selected mating hardware and supplied parts
  • Review your mounting datums and service envelope
  • Specify ports, seal lands and connector alignment
  • Agree component and platform acceptance separately
  • Confirm the sample and acceptance evidence
Illustrative mating hardware and boundary concept, not documentary company or customer photography

Mating hardware and boundary

Identify the selected rack manifold quick disconnect and the machined adapter or bracket included in your order. List rack liquid cooling fittings supplied or specified by your approved connector vendor; confirm who accepts the complete connection.

Illustrative ports and rack installation concept, not documentary company or customer photography

Ports and rack installation

Define the rack manifold connection interface with controlled port locations, sealing method, mounting datums, fitting access, hose routing and the installation envelope. Review the liquid cooling quick disconnect interface against the actual mating specification.

Illustrative alignment and movement concept, not documentary company or customer photography

Alignment and movement

For blind mate liquid cooling connectors selected by your system designer, provide guide features, mating direction, allowed positional and angular offset, any designed float and the locking arrangement. No universal interchangeability is assumed.

Illustrative drawings and sample scope concept, not documentary company or customer photography

Drawings and sample scope

Your rack cooling interface drawing requirements should include the controlled revision, datum scheme, port schedule, mating parts, material, final condition and agreed records. Identify unresolved interfaces before sample manufacture.

Illustrative engineering concepts

Define 4 Supplied Scopes for Your Rack Interface

Distinguish the machined parts on your drawing from selected finished connectors and their qualification.

Illustrative engineering concepts; generic connector housings show mating context.

Define Your Machined Part Around the Selected Connector

MATING SPECIFICATION + DATUMS↓COMPONENTS & CONNECTIONS↓SAMPLE & AGREED CHECKS↓APPROVED FINISHED PART

Rack cooling adapter manufacturing and liquid cooling connector machining cover the parts defined on your released drawings. Your custom liquid cooling adapters should identify mating specifications, material, sealing geometry, mounting datums and the delivered state. Separate these rack cooling adapters from the selected finished connector and its qualification; manufacturing an interface part does not qualify an entire quick-disconnect assembly.

  • Define the supplied parts, material and connection boundary.
  • Review your critical interfaces in their final production state.
  • Agree sample evidence before repeat-order release.
Compare thermal technology routes →

Interface background: CPC liquid-cooling connection guide → · OCP rack manifold requirements white paper →. General industry references do not establish membership, certification, connector qualification or adoption of their numeric limits.

Compare Your Wetted Material References

Choose material with your coolant, connected metals, seals, mass and manufacturing route in view. These stock references do not establish corrosion compatibility, a pressure rating or manifold flow performance.

Thermal conductivity reference

6061-T6 · 25°C167 W/(m·K)
304 / 1.4301 · 20°C15 W/(m·K)
316L / 1.4404 · 20°C15 W/(m·K)

A header distributes coolant; higher bulk conductivity alone does not make its branches more balanced.

Density reference

6061 aluminum2.7 g/cm³
304 stainless steel7.9 g/cm³
316L stainless steel8.0 g/cm³

Estimate mass using your finished volume. Confirm exact grade, product specification and required condition with the purchasing documents.

6061 selected composition limits · weight %
Grade / European referenceSiFeCuMnMgZnAl
6061 · EN AW-6061 · AlMg1SiCu0.40–0.80≤0.700.15–0.40≤0.150.80–1.20≤0.25Balance

6061 additional selected limits: Cr 0.04–0.35%, Ti ≤0.15%; other elements ≤0.05% each / ≤0.15% total. Hydro reference, not a finished manifold certificate.

Stainless steel selected typical composition · weight %, not specification limits
Reference gradeEuropean identifierUNSCCrNiMo
304EN 1.4301S304000.0418.18.1—
316LEN 1.4404S316030.0217.210.12.1

Outokumpu Core/Supra Table 1 typical composition and Table 7 physical references. Dash means not listed in the selected summary, not zero. European identifiers aid drawing review; substitutions and final purchasing limits require approval.

Sources: Hydro 6061 → · Outokumpu Core 304 → · Outokumpu Supra 316L →

3 Views for Your Alignment and Connection Acceptance

Review the assembly stack, test boundary and service envelope. The numeric graphic is chosen arithmetic, not an LK MFG tolerance, allowable connector offset or qualification report.

1 · Chosen alignment stack

Chosen bracket contribution0.1 mm
Chosen adapter contribution0.15 mm
Chosen mounting contribution0.2 mm
Worst-case sum of magnitudes0.45 mm

Chosen example: 0.10 + 0.15 + 0.20 = 0.45 mm worst-case positional stack. These are invented calculation inputs, not measured parts or recommended tolerances. Actual datum directions, angular effects, designed float and allowable mismatch follow the design owner and selected connector specification.

2 · State the test boundary

BARE MACHINED PART + PLUGS↓SPECIFIED FITTINGS + SEALS↓DELIVERED INTERFACE ASSEMBLY

Identify which state is inspected and tested. Record the mating hardware, medium, conditions, leakage criterion and pressure-test scope. Part acceptance and complete connector qualification remain separate decisions.

3 · Preserve service access

MATING DIRECTION + GUIDE FEATURES↓LOCKING + TOOL + HOSE CLEARANCE↓REMOVAL SEQUENCE + RESTRAINT

Review the installed position and maintenance operation together. Confirm the selected connector travel, locking access, hose envelope and bracket restraint against the actual rack assembly.

Review Your Surface and Cleanliness Requirements

Separate mounting datums, sealing interfaces and wetted passages. Confirm the specified final condition with the mating assembly.

Illustrative solid mounting datum face on a rack interface bracket concept, not documentary company or customer photography

Define your mounting footprint, datum scheme and final inspection state.

A finish is not a universal cooling improvement. Confirm its purpose, compatibility and inspection state. Review surface finishing options →

Illustrative engineering concepts

Define Your Functional Features

Put the dimensions that control sealing, assembly fit and heat transfer on your drawing.

Illustrative sectioned rack adapter and mounting flange concept, not documentary company or customer photography

Illustrative machined rack adapter concept

Mounting footprint

Datum scheme, mating position and bracket restraint

Ports and seals

Thread designation, seal land and fitting engagement

Mounting datums

Hole pattern, datum scheme and tool access

Guides and clearances

Mating direction, service access and cleaning scope

Final condition

Flatness, masking, protected interfaces and inspection state

Resolve 6 Design Risks Before Your Order

Resolve port sealing, alignment, mounting access, compatibility, specified tests and prototype acceptance before release.

Threads and sealing lands

Specify rack cooling interface port threads by the selected standard, designation, engagement and sealing method. Define rack cooling interface sealing surfaces by the controlled datum, geometry, surface condition and inspection state; matching a thread name alone does not approve the seal.

Your input

Controlled drawing and the relevant service conditions.

Your acceptance

Agreed method, inspection state, limits and required records.

Illustrative threads and sealing lands review for rack cooling interface parts concept, not documentary company or customer photography

Illustrative engineering concept

5 Checkpoints from Drawing to Repeat Supply

Drawing review

Confirm revision, interfaces and operating inputs.

Route review

Agree materials, joining and final machining.

Sample build

Review the finished component and assembly fit.

Agreed checks

Assess specified dimensions, joints and test records.

Production release

Release the accepted revision, packaging and repeat-order scope.

Approve the Interface Part and Preserve the Qualification Boundary

Illustrative rack cooling interfaces dimensional inspection concept, not a customer part

Illustrative component concept

Your custom rack cooling interface quote should define the machined parts, selected mating hardware, final inspection state, quantities and supplied records. Confirm drawing revision, material identity, measured interface dimensions and the agreed assembly or test evidence. Component inspection does not establish the qualification, cycle life, spillage performance or universal compatibility of a finished connector.

  • Material identity and drawing revision
  • Mounting datum faces, mounting and interface dimensions
  • Specified joining and test evidence
  • Port protection, packaging and shipment release
Review quality requirements →

Review Your Rack Interface in Its Installed Position

These are part and integration review contexts, not qualified complete connectors, installed customer projects or universal compatibility claims.

Illustrative rack adapter and connector mounting integration fixture concept, not documentary company or customer photography

Rack manifold ports

Match selected fittings, sealing geometry and service space.

Blind-mate mounts

Control guides, alignment, locking and designed float.

Server tray edges

Review removal direction and nearby obstructions.

Adapter prototypes

Check released datums and mating dimensions.

Service replacements

Match the exact mating revision and installed envelope.

Mounting brackets

Define support, fasteners and mechanical responsibility.

Loop interfaces

Agree the supplied fitting and hose boundary.

Approval fixtures

State inspection and connection-check methods.

Review data center component boundaries →

6 Inputs for Your Rack Cooling Interfaces Quote

  1. Controlled adapter or bracket drawings + revision
  2. Selected mating connector specifications + supplier
  3. Port schedule, seal geometry + datum scheme
  4. Alignment, designed float, locking + service envelope
  5. Coolant, wetted materials + final cleanliness
  6. Quantities, supplied assembly boundary + acceptance records

Ask your quote to separate component manufacturing, joining, finishing, inspection and any independently agreed validation. The drawing review confirms availability, quantities and delivery scope.

Answers Before You Specify

What drawings are needed to quote a rack cooling interface part?

Provide the controlled part drawing and CAD, revision, datum scheme, ports and mating specification, bracket or mounting envelope, material and final finish, quantities and required records. Mark the supplied interface boundary and any unresolved mating details.

Does machining a rack cooling interface qualify a quick disconnect?

No. Inspection of the machined adapter, port or bracket covers its stated drawing and acceptance. Qualification of the complete connector, including mating, lifecycle, fluid release and service conditions, belongs to the selected connector specification and its agreed qualification owner.

How should blind mate cooling interface alignment be specified?

The design owner should state mating direction, positional and angular allowances, guides, locking constraints and any designed floating travel. Review the complete assembly stack and acceptance method; do not infer limits from a generic connector photograph.

Should rack cooling interfaces be leak tested with mating fittings?

Define the test assembly to match the supplied boundary. State whether selected fittings, seals, plugs and brackets are installed, together with the method, medium, conditions and leakage limit. A bare-part test and a final connection test cover different boundaries.

Which coolant details affect rack cooling interface material selection?

Provide coolant formulation, concentration, temperature range and the wetted metals, coatings and seals of the connected system. Include cleaning or preservation chemicals where relevant. Confirm compatibility against the system and connector-supplier requirements.

What records are needed to approve a rack cooling interface prototype?

Agree the controlled drawing, material identity, final dimensions and datums, mating or installation review, cleanliness, specified leak or pressure checks and any separate validation. Identify the supplied reports and the person or team approving each scope.